The magnet coil is rated 24 VDC, with a closing and holding power of 2.3 W — a low-hold design that reduces heat buildup in the panel and lets you use a smaller DC supply than an equivalent AC coil. If your application is AC-3 (normal starting of squirrel-cage motors), the contactor handles higher currents; the AC-4 figure is the conservative one for high-stress cycles. The auxiliary contact block (integrated) carries 10 A at 24 VDC, 6 A at 230 V, and 3 A at 400 V — these are the ratings for the built-in N/O and N/C contacts used in control logic or signaling. Short-circuit coordination is specified: type 2 coordination requires a gL/gG fuse of 20 A; type 1 allows up to 35 A. That means with a 20 A fuse, the contactor remains usable after a fault; with a 35 A fuse, it may need replacement but the circuit clears.
Main current circuit terminals are screw-type, accepting 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. This covers most panel wiring up to 4 mm² without needing ferrule adapters.
Environmental and Protection
Above that, expect reduced dielectric strength and switching capacity.