It occupies 45 mm of panel width and 73 mm depth, with spring-loaded terminals on the main circuit accepting 2x (0.25 to 2.5 mm²) solid or stranded conductors.
Motor power ratings land at 5.5 kW at both 500 V and 690 V — that covers 400 V class motors with headroom for 690 V line-fed drives. DC switching is covered across a range of voltages: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. If you're switching DC solenoids or brake coils, size the contactor against the DC curve, not the AC motor rating.
Side-by-side mounting is permitted (no derating gap required), so you can pack multiple contactors across the DIN rail at the 45 mm pitch. The spring-loaded terminals on the main circuit accept 2x (0.25 to 2.5 mm²) or 2x (24 to 14 AWG) — strip length and ferrule size per standard practice for cage-clamp terminations.