S0 frame, 3 NO main contacts, 24 V 50 Hz coil
The 45 mm width and 85 mm height mean it fits a standard 4-module-wide panel slot. Front protection is IP20; the terminals themselves are IP00, so the contactor needs enclosure protection against accidental contact with live parts.
Motor switching ratings and coordination
For AC-2 duty at 400 V it handles 4 kW, and for AC-4 (reversing/inching) at 400 V it's rated 8.5 A. At 500 V it switches 4.5 kW motor loads; at 690 V it switches 5.5 kW. Type 1 coordination requires a 63 A gL/gG fuse; Type 2 coordination needs a 25 A gL/gG fuse.
The 140 mm depth fits standard 200 mm deep enclosures.