Motor duty and switching capability
At 500 V it handles 4.5 kW, and at 690 V it handles 5.5 kW, both under AC-3 duty. The auxiliary contact block (2 NO) is rated for 10 A at 24 V DC, 6 A at 230 V, and derates down to 0.3 A at 220 V DC — watch the DC switching curve if you're breaking inductive loads on the aux side.
Screw-type terminals on the main circuit accept 2x (1 to 2.5 mm²) stranded or 2x (2.5 to 6 mm²) solid, with a maximum of 2x 10 mm² or 1x 8 AWG. The auxiliary terminals take 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). Side-by-side mounting is allowed with a 6 mm gap to adjacent devices — no derating required if ambient stays within -25 to +60 °C.