For motor loads, it is rated 4.5 kW at 400 V in AC-2 duty and 5.5 kW at 690 V. Auxiliary contact ratings are voltage-dependent: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V — the lower current at higher DC voltages reflects the arc-extinction limit of the contact gap.
The contactor occupies a 45 mm wide DIN-rail footprint, 85 mm tall, 91 mm deep. Main-circuit screw terminals accept 2x (1 to 2.5 mm²) stranded or 2x (2.5 to 6 mm²) solid, with a maximum of 2x 10 mm². Auxiliary terminals accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, max 2x (0.75 to 4 mm²). AWG equivalents for main contacts are 2x (16 to 12) and 2x (14 to 10), with a single 8 AWG maximum. Short-circuit coordination: with type 2 coordination, use a gL/gG fuse rated 25 A; with type 1 coordination, the fuse can be 63 A.