SIRIUS S0 power contactor — 3RT1023-1AP04-ZX95
Rated operational current at AC-2 duty at 400 V is 4 kW; at AC-4 at 400 V it handles 8.5 A.
Front face carries IP20 protection — safe for finger contact in an enclosed panel; the terminal area is rated IP00, so live parts are exposed during wiring. Wire capacity on the main circuit: solid conductors accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²). Stranded conductors: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), max 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), 1x 8. For type 1 coordination, use a 63 A gL/gG fuse; for type 2, a 25 A gL/gG fuse is required.