SIRIUS S0 power contactor, 220 VAC coil
Both main and auxiliary/control circuits use screw-type terminals. Main terminals accept 2x (1.0–2.5 mm²) solid/stranded, 2x (2.5–6 mm²), or max 2x 10 mm². Auxiliary terminals accept 2x (0.5–1.5 mm²) solid, 2x (0.75–2.5 mm²), or max 2x (0.75–4 mm²). AWG equivalents are listed for both. Coil power draw is 5.4 W DC for both closing and holding — a single value, meaning the magnet circuit does not drop to a lower hold power. This matters for control-transformer sizing and DC-supply budgeting in the panel.
For Type 1 coordination (welding allowed but no fire risk), the fuse rating is gL/gG 63 A. These are the manufacturer's specified limits for the main circuit. Storage temperature range is wider but not specified here — the operating range governs panel placement and derating.
Switching ratings and load types
AC-2 duty (slip-ring motors) at 400 V: 4 kW. AC-4 duty (plugging/inching) at 400 V: 8.5 A. DC switching ratings are provided per voltage: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, 3 A at 400 V. These cover the auxiliary contact block's DC load-breaking capability — relevant for PLC inputs, DC brake coils, or indicator lamps. Motor power ratings at higher line voltages: 4.5 kW at 500 V, 5.5 kW at 690 V — typical for 500 V or 690 V industrial networks (mining, marine, heavy industry).
Substance prohibitance date is listed as 01.07.2006, aligning with RoHS compliance (EU RoHS took effect July 2006).