The 48 VDC coil draws 5.4 W both on pick-up and hold, which simplifies the DC supply sizing — no inrush spike to budget for. Motor power ratings reach 4.5 kW at 500 V and 5.5 kW at 690 V, covering common European and export voltage levels. The IP20 front protection keeps fingers and tools out of the live terminals inside the enclosure; the terminals themselves are rated IP00, so the contactor must live inside a cabinet, not out on the plant floor.
Environment and wiring
Main circuit terminals accept solid conductors from 2x (0.5... 1.5 mm²) up to 2x (0.75... 4 mm²), and stranded conductors from 2x (1... 2.5 mm²) up to 2x 10 mm². That range covers standard motor feeder cables up to about 6 AWG without lugging. Side-by-side mounting is allowed with a 6 mm gap to the side, keeping panel density high. Short-circuit coordination is specified: for Type 2 coordination (limited damage after a fault), use a gL/gG fuse rated 25 A; for Type 1 (replace contactor after fault), use 63 A.