The 4 kW AC-2 rating at 400 V covers slip-ring motor starting, a less punishing cycle but still a real motor load, not a resistive heater.
Panel Fit & Wiring
Screw terminals accept solid or stranded conductors: 2x (0.25 to 2.5 mm²) for control wiring, and up to 2x 10 mm² or 1x 8 AWG for the main circuit. IP20 on the front, IP00 at the terminals: the terminal area is live and needs finger-safe shrouding in the panel build.
Coordination & Protection
Type 1 coordination (contactor may be damaged but no fire risk) allows a 63 A gL/gG fuse.