Lead — integrator note
AC-4 at 400 V is 8.5 A, for reversing or inching duty. At 690 V the contactor handles 5.5 kW (AC-3). Pollution degree 3 means it tolerates conductive dust in industrial enclosures.
Coordination and wiring
For type 1 coordination (device may be damaged but safe), use 63 A. Main circuit terminals accept 2x (0.25 to 2.5 mm²) solid or 2x (1 to 2.5 mm²) stranded, up to 2x 10 mm². AWG equivalents are 2x (16 to 12) solid, 2x (14 to 10) stranded, or 1x 8.