Skip to main content
Siemens 3RT1023-3BB40-1AA0 — Contactors

Siemens 3RT1023-3BB40-1AA0 SIRIUS Power Contactor, 24 VDC Co

MPN3RT1023-3BB40-1AA0

Siemens SIRIUS power contactor, Size S0, 24 V DC coil, screw-type terminals, 45 mm width, IP20 front, current production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1023-3BB40-1AA0 — Identification
ParameterValue
Contactor frame sizeS0
3RT1023-3BB40-1AA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V4.5 kW
Rated value @ 690 V5.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1023-3BB40-1AA0 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT1023-3BB40-1AA0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1023-3BB40-1AA0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 63 A
Short-circuit coordination type 2, fusefuse gL/gG: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1023-3BB40-1AA0 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Side-by-side mountingYes
3RT1023-3BB40-1AA0 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1023-3BB40-1AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1023-3BB40-1AA0 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth101 mm

Product details

Siemens SIRIUS 3RT1023-3BB40-1AA0 — Power Contactor, Size S0, 24 VDC Coil

Rated for AC-3 motor duty, it handles 4.5 kW at 500 V and 5.5 kW at 690 V, with an AC-4 breaking current of 8.5 A at 400 V for reversing or inching applications. The coil draws 5.4 W during both pick-up and hold, so the control transformer sizing is straightforward — no inrush spike to over-spec for. For short-circuit protection, Type 1 coordination calls for a 63 A gL/gG fuse; Type 2 requires 25 A.

Side-by-side mounting is permitted with zero gap, which simplifies busbar and wiring runs in a multi-contactor motor control center. The IP20 front protection means the contactor is safe for finger contact inside a closed panel; the terminals themselves carry IP00, so live parts are exposed only during wiring. Depth of 101 mm leaves clearance for standard 120 mm deep enclosures.

Auxiliary Contact Switching Capacity

The integrated auxiliary contacts (1 NO + 1 NC, instantaneous) are rated for switching at various control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. These ratings cover most PLC output and relay interface loads without an additional interposing relay.

Frequently asked questions

What are the key motor power ratings for the 3RT1023-3BB40-1AA0?

In AC-3 duty it is rated for 4.5 kW at 500 V and 5.5 kW at 690 V. For AC-4 reversing duty, the breaking current is 8.5 A at 400 V.

What is the coil voltage and power consumption?

The magnet coil is rated 24 V DC, consuming 5.4 W for both closing and holding — no inrush peak to account for in the control transformer sizing.

What fusing is required for Type 1 and Type 2 coordination?

Type 1 coordination requires a 63 A gL/gG fuse; Type 2 coordination requires a 25 A gL/gG fuse.

Where can I buy the 3RT1023-3BB40-1AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

MPN
3RT1023-3BB40-1AA0