For motor switching, the AC-3 rating drives the selection: 5.5 kW at 400 V, 7.5 kW at 500 V, and 7.5 kW at 690 V. The auxiliary contact block handles 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — enough for a PLC input or relay coil. Fuse coordination is specified: Type 2 coordination requires a 25 A gL/gG fuse; Type 1 coordination allows a 63 A gL/gG fuse. The contactor is rated for a mechanical life of 10,000,000 operations, and the operating temperature range is -25 to +60 °C.
The contactor accepts solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²). For the main circuit, it accepts 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), and max 2x 10 mm². AWG equivalents for the main contacts are 2x (16 to 12), 2x (14 to 10), and 1x 8. The enclosure offers IP20 on the front and IP00 at the terminals — standard for a panel-mounted contactor where the busbars or wiring provide additional protection.