It mounts on a 35 mm DIN rail per DIN EN 50022, with a 45 mm width that fits standard panel layouts.
The AC-2 rating at 400 V is 5.5 kW, so this contactor switches wound-rotor motor loads up to that power level without excessive contact wear. The AC-4 rating at 400 V is 12.5 A, covering plugging and inching duty cycles where the contacts make and break under load. Pollution degree 3 means the contactor is designed for conductive environments typical of industrial atmospheres.