Rated for AC-2 duty at 5.5 kW at 400 V, it handles slip-ring motor loads; the AC-4 rating of 12.5 A at 400 V covers plugging and inching duty cycles.
The 45 mm wide S0 frame occupies three DIN-rail pitches. Side-by-side mounting is permitted with 6 mm spacing to adjacent devices for heat dissipation. Screw terminals accept solid or stranded conductors: main contacts take 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), or max. 2x (0.75–4 mm²); auxiliary circuits use 2x (1–2.5 mm²) or max. 2x 10 mm². AWG equivalents are 2x (16–12), 2x (14–10), or 1x 8 for the main circuit.
Coordination & Protection
For Type 2 coordination (contactor remains operational after a fault) the fuse is gL/gG 25 A.