Siemens 3RT1024-1AP04-ZW96 SIRIUS Power Contactor, S0, 3 NO,

MPN3RT1024-1AP04-ZW96

Siemens SIRIUS 3RT1024-1AP04-ZW96 power contactor, size S0, 3 NO main contacts, screw terminals, 7.5 kW at 500/690 V, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1024-1AP04-ZW96 — Identification
ParameterValue
Contactor frame sizeS0
3RT1024-1AP04-ZW96 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V12.5 A
Rated value @ 400 V3 A
Rated value @ 500 V7.5 kW
Rated value @ 690 V7.5 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1024-1AP04-ZW96 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz230 V
3RT1024-1AP04-ZW96 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1024-1AP04-ZW96 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 63 A
Short-circuit coordination type 2, fusefuse gL/gG: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1024-1AP04-ZW96 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1024-1AP04-ZW96 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1024-1AP04-ZW96 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1024-1AP04-ZW96 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth140 mm

Product details

Rated at 7.5 kW at both 500 V and 690 V, this contactor handles AC-2 duty at 400 V up to 5.5 kW and AC-4 at 400 V up to 12.5 A — the AC-4 figure governs reversing or inching applications where the contactor breaks the motor current directly. The front of the contactor carries an IP20 rating, while the terminals themselves are IP00 — standard for panel-mount contactors where the enclosure provides the overall protection.

Solid conductors accepted: 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max. 2x (0.75... 4 mm²). Stranded: 2x (1... 2.5 mm²), 2x (2.5... 6 mm²), max. 2x 10 mm². AWG equivalents for main contacts: 2x (16... 12), 2x (14... 10), 1x 8. Side-by-side mounting is permitted — no derating gap required. Pollution degree 3 (industrial environment, conductive pollution possible).

Coordination and auxiliary ratings

Auxiliary contact ratings at various control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 1 A at 110 V, 0.3 A at 220 V, 2 A at 60 V. The coil operates at 50 Hz with a voltage tolerance of 0.8 to 1.1 times the rated value.

Frequently asked questions

Where can I buy 3RT1024-1AP04-ZW96 and get a price?

The part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the depth of 3RT1024-1AP04-ZW96?

Depth is 140 mm, which is the critical dimension for enclosure clearance behind the DIN rail.

What solid wire sizes does the 3RT1024-1AP04-ZW96 accept?

Solid conductors: 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max. 2x (0.75... 4 mm²). Stranded: 2x (1... 2.5 mm²), 2x (2.5... 6 mm²), max. 2x 10 mm².

Will 3RT1024-1AP04-ZW96 drop into a panel specified around 3RT1023-1AL20?

Both are S0-size SIRIUS contactors sharing the same 45 mm width and DIN-rail footprint, so mechanical fit is identical. Verify the coil voltage and auxiliary configuration against the original spec before swapping.

What compliance documentation does Siemens provide for 3RT1024-1AP04-ZW96?

The part carries a reference code per DIN EN 81346-2 (Q). Standard Siemens SIRIUS documentation includes RoHS and REACH declarations; UL and IEC certifications are typically listed on the nameplate and in the manufacturer's declaration package.

MPN
3RT1024-1AP04-ZW96