It is rated for 7.5 kW at both 500 V and 690 V, and carries an AC-4 breaking current of 12.5 A at 400 V — so it handles reversing or inching duty where the contactor breaks full motor current, not just the running load.
The S0 frame measures 45 mm wide by 85 mm high by 90 mm deep, so it fits standard 45 mm DIN-rail pitch. DC switching capability is specified per voltage: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, and 6 A at 230 V. The screw terminals accept 2x (0.25 to 2.5 mm²) solid or stranded, up to 2x 10 mm² max — covers most control and power wiring in a standard panel. Fuse coordination: with type 2 coordination (no welding on short circuit), use gL/gG 25 A fuses; with type 1 coordination (allow contactor replacement after fault), use gL/gG 63 A fuses. This is the spec your panel designer needs for the short-circuit protection scheme.