The 220 V AC coil is the control voltage — match it to your control transformer or PLC output card. At 500 V and 690 V, the motor power rating is 7.5 kW, so this contactor handles a standard 7.5 kW induction motor on a 500 V or 690 V line. The auxiliary contact block is rated for switching at various control voltages: 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. That covers pilot duty for PLC inputs, relay coils, and indicator lamps.
Side-by-side mounting is permitted with no derating, which saves rail space in dense cabinets. The front of the contactor is IP20, meaning finger-safe for panel installation. Main circuit terminals are screw-type, accepting 2x (1 to 2.5 mm²) solid/stranded, 2x (2.5 to 6 mm²), or up to 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), or 1x 8. Solid wire range is 2x (0.25 to 2.5 mm²).
Coordination & Environment
This matters for selectivity studies and SCCR compliance. Coil consumption: 5.4 W closing power and 5.4 W holding power (DC). The holding power is the same as closing, so the coil driver sees a constant load — no power-save circuit inside this variant.