Rated for 10 kW at 500 V and 11 kW at 690 V, this contactor handles the motor starting and stopping duties common on pumps, fans, and conveyors in a 400 V to 690 V three-phase system. The AC-2 rating at 400 V is 7.5 kW, and the AC-4 rating at 400 V is 15.5 A — the AC-4 figure governs reversing or inching duty where the contactor makes and breaks stalled-rotor current.
Main circuit terminals accept screw-type connections: solid conductors from 2x (0.5 to 1.5 mm²) up to 2x (0.75 to 4 mm²), and stranded conductors from 2x (1 to 2.5 mm²) up to 2x (2.5 to 6 mm²), with a maximum of 2x 10 mm². AWG equivalents are 2x (16 to 12) solid and 2x (14 to 10) stranded, with a single 8 AWG maximum. The terminal IP00 rating means the connection points are not touch-protected — the panel enclosure provides that barrier.
For Type 2 coordination (contactor remains usable after a fault), the fuse is gL/gG 25 A. These values guide the selection of motor-protective circuit breakers or fuses in the feeder.