Siemens 3RT1025-1AH04 — Contactors

Siemens 3RT1025-1AH04 SIRIUS Power Contactor, S0, 3NO, 15.5A

MPN3RT1025-1AH04

Siemens SIRIUS 3RT1025-1AH04 power contactor, size S0, 3 NO main contacts, 15.5 A AC-4 at 400 V, 7.5 kW AC-2, 11 kW at 690 V, screw terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1025-1AH04 — Identification
ParameterValue
Contactor frame sizeS0
3RT1025-1AH04 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V10 kW
Rated value @ 690 V11 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1025-1AH04 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz48 V
3RT1025-1AH04 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1025-1AH04 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 63 A
Short-circuit coordination type 2, fusefuse gL/gG: 25 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1025-1AH04 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1025-1AH04 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1025-1AH04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1025-1AH04 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth140 mm

Product details

The 3RT1025-1AH04: Three NO main contacts, zero NC. The AC-4 rating of 15.5 A at 400 V governs plugging and inching duty — the high-stress switching that wears contacts fastest. At 690 V it handles 11 kW, so it suits 400 V and 690 V distribution without a frame size jump. The AC-12 operating current of 10 A covers resistive loads like heater banks.

Side-by-side mounting is permitted, so multiple contactors pack tightly on the rail without derating gaps.

Accepts 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid. For stranded: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), or max 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), or 1x 8. Standard panel-builder practice: keep the gland plate clearance for the 140 mm depth.

This matters when the panel designer has already locked in a fuse size — the 25 A limit for Type 2 is the tighter constraint.

Environmental range

Maximum installation altitude is 2 000 m — above that, derate for air density. The coil holds at 24 V rated value drawing 10 A (inrush), dropping to lower hold values. At 60 V the rated current is 2 A; at 110 V it is 1 A; at 220 V it is 0.3 A.

Frequently asked questions

What are the key ratings for this contactor?

Three NO main contacts. AC-4 rating is 15.5 A at 400 V. AC-2 motor rating is 7.5 kW at 400 V. At 690 V it handles 11 kW. The AC-12 resistive rating is 10 A. Frame size S0, 45 mm wide.

What is the mounting method?

Screw or snap-on mounting onto 35 mm DIN rail per EN 50022. Side-by-side mounting is allowed.

What wire sizes does the screw terminal accept?

Solid: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), max 2x 10 mm². AWG: 2x (16 to 12), 2x (14 to 10), 1x 8.

What fuse coordination is required?

Type 2 coordination requires a gL/gG 25 A fuse upstream. Type 1 coordination allows up to gL/gG 63 A.

MPN
3RT1025-1AH04