At 690 V it is rated 11 kW, and at 500 V, 10 kW, giving the buyer a clear kW-per-voltage map for motor sizing.
Termination and wiring
Main circuit terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²) solid or stranded wire. For the main current path, larger cross-sections are supported: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), and max 2x 10 mm². AWG equivalents for the main contacts are 2x (16 to 12), 2x (14 to 10), and 1x 8. The control circuit terminals handle 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²).
Protection and coordination
For Type 2 coordination (limited damage under short circuit) the required fuse is gL/gG 25 A. For Type 1 coordination (device must be replaced after fault) the fuse can be up to 63 A gL/gG. This lets the panel designer balance protection level with fuse availability.