Side-by-side mounting is allowed without derating, so you can pack multiple units on a rail for multi-motor groups. Main-circuit terminals are screw-type, accepting up to 2x 10 mm² stranded or 1x 8 AWG.
Duty ratings and coordination
Type 1 coordination requires a 63 A gL/gG fuse; Type 2 coordination needs a 25 A gL/gG fuse.
Environmental and auxiliary ratings
The front of the terminal is IP20 (finger-safe); the terminal itself is IP00 (open-terminal). Auxiliary contact ratings cover DC loads: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, and 6 A at 230 V AC.