SIRIUS S0 power contactor — panel fit and ratings
Rated for motor switching at 11 kW on a 690 V three-phase supply under AC-3 duty, and 7.5 kW at 400 V AC-2. For resistive loads (AC-1), the maximum operating current is 10 A. DC switching capability is given per voltage: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V.
Coordination and wiring
Main circuit terminals are screw-type, accepting solid conductors up to 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and a maximum of 2x (0.75 to 4 mm²). For stranded wire, the range is 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), and max 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), and 1x 8. Strip length and torque specs should follow the standard SIRIUS S0 terminal data. Type 2 coordination requires 25 A.