SIRIUS S0 power contactor for motor and resistive loads
The contactor is rated for AC-3 motor switching: 10 kW at 500 V and 11 kW at 690 V, with an AC-4 rated operational current of 15.5 A at 400 V for reversing or inching duty.
Type 1 coordination allows a 63 A gL/gG fuse, which permits the contactor to be replaced after a fault.
Termination and wiring
Main circuit terminals accept solid conductors: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), max 2x (0.75–4 mm²). For stranded or ferruled wire: 2x (1–2.5 mm²), 2x (2.5–6 mm²), max 2x 10 mm². AWG equivalents: 2x (16–12), 2x (14–10), 1x 8. The auxiliary contact block (3RT1025-1BB48-0QA2 includes one instantaneous N/O + N/C) has its own terminal ratings.