The coil is 230 V AC, with a closing and holding power of 5.4 W DC, so the control transformer needs to cover that draw.
Motor switching and contact ratings
At 500 V it handles 10 kW and at 690 V it handles 11 kW, so it can serve 690 V line applications up to that power. The auxiliary contact block carries two instantaneous contacts rated at 10 A at 24 V, 6 A at 230 V, and 0.3 A at 220 V DC. That covers signalling and interlocking in the control circuit.
Short-circuit coordination and environment
With type 2 coordination, the required fuse is gL/gG 25 A; with type 1 coordination it's 63 A. That dictates the upstream protection selection for the motor branch circuit. Side-by-side mounting is permitted, which saves rail space when ganging multiple contactors.