Rated for 10 kW at 500 V and 11 kW at 690 V, this contactor handles a 3-phase motor up to that power range.
The 90 mm depth means you need at least that much clearance behind the panel door for the arc chamber and terminals. Main circuit terminals are screw-type, accepting solid conductors from 0.25 to 2.5 mm² (two per clamp) and stranded up to 2x 6 mm² or a single 10 mm². AWG equivalents run from 2x 16-12 down to 1x 8. That's enough for the motor leads this contactor is sized for.
Protection and coordination
For Type 1 coordination (contactor may need replacement after a fault), the fuse can be 63 A. This lets a panel builder choose between protecting the contactor or protecting the circuit with a larger fuse. The contactor is rated for operation up to 2,000 m altitude without derating. Above that, expect reduced dielectric strength and cooling air density.