Part identity and key ratings
The contactor is rated for motor switching: at AC-3 duty on 400 V it handles 7.5 kW, and at AC-4 on 400 V it carries 15.5 A. For resistive loads (AC-12) the maximum operating current is 10 A. At 690 V it is rated for 11 kW (AC-3). Mechanical endurance is listed at 10 million operating cycles, typical for this class of IEC contactor.
Main circuit terminals are screw-type, accepting solid or stranded conductors: 2x (0.25–2.5 mm²), 2x (1–2.5 mm²), 2x (2.5–6 mm²), or a single 10 mm². AWG equivalents are 2x (16–12), 2x (14–10), and 1x 8. Pollution degree 3 (industrial environment).
Protection and coordination
For Type 1 coordination (contactor may need replacement) the fuse can be up to 63 A gL/gG.