Panel builders can land screw-type terminals on the main circuit — accepts 2x (0.25...2.5 mm²) solid or up to 2x 10 mm² stranded, with AWG equivalents 2x (16...12) or 1x 8.
Motor duty and coordination
In AC-2 duty (slip-ring motors, wound-rotor) at 400 V, the contactor switches 7.5 kW. For AC-4 (plugging, inching) the same voltage yields 15.5 A. The S0 frame keeps the width at 45 mm — fits standard panel layouts without crowding. Type 2 coordination requires a 25 A gL/gG fuse; Type 1 allows 63 A. Pollution degree 3 suits industrial environments with conductive deposits.
The built-in auxiliary contact block handles 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for PLC inputs or small relays. At 220 V DC the rating drops to 0.3 A, so confirm DC load current before wiring.