Rated for motor switching: 11 kW at 690 V AC-3, 10 kW at 500 V AC-3, and 7.5 kW at 400 V AC-2. The coil draws at 50 Hz between 0.8 and 1.1 times its rated voltage, so it picks up reliably on a 230 V line even if the supply sags slightly.
Main circuit terminals are screw-type, accepting 2x (0.25 to 2.5 mm²) solid or 2x (1 to 2.5 mm²) stranded, with a maximum of 2x 10 mm². AWG equivalents are 2x (16 to 12) solid, 2x (14 to 10) stranded, or 1x 8. Strip length and torque follow standard Siemens S0 practice. For type 2 coordination (limited overcurrent damage), use a gL/gG fuse rated 25 A. This matters when sizing branch protection in a motor control center.