The screw-type terminals on the main circuit accept up to 2x 10 mm² stranded or 1x 8 AWG, which covers most motor branch wiring up to 7.5 kW.
Type 1 coordination requires a 63 A gL/gG fuse upstream; type 2 coordination calls for 25 A. That's the selectivity headroom you need for the branch circuit — type 2 keeps the contactor reusable after a short, type 1 may damage it.
Integration notes
The S0 frame is 45 mm wide, 85 mm tall, 90 mm deep — fits a standard 45 mm DIN cell. Front IP20 means finger-safe; the terminals themselves are IP00, so keep live parts behind a panel door or cover.