In AC-3 duty (squirrel-cage motor starting) at 400 V, this contactor is rated for 7.5 kW; at 500 V it handles 10 kW, and at 690 V it reaches 11 kW.
Switching capacity on the coil side: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, 3 A at 400 V. The built-in varistor suppressor clips the inductive kick, which saves adding an external diode or RC snubber on the panel layout.
Coordination and fusing
For Type 2 coordination (limited contact damage, minimal downtime) it's gL/gG 25 A. That's the fuse the panel builder needs to spec — not the contactor's own rating.
Environmental and mounting limits
The contactor body carries IP20 on the front (finger-safe), while the terminals themselves are IP00 — so the panel enclosure provides the touch protection. Side-by-side mounting is permitted with 6 mm spacing at the side.
Termination details
Main circuit terminals are screw-type, accepting 2x (0.25 to 2.5 mm²) solid or 2x (1 to 2.5 mm²) stranded, with a maximum of 2x 10 mm². AWG equivalents: 2x (16 to 12) solid, 2x (14 to 10) stranded, or 1x 8. That covers standard panel wire sizes up to about 8 AWG for the power circuit.