It is rated for 11 kW at 500 V and 11 kW at 690 V in AC-3 duty, which covers the majority of standard three-phase induction motors at those voltage levels. The coil is a 24 V 50/60 Hz pickup, so it drops into any 24 VAC control circuit without worrying about frequency mismatch.
In AC-4 duty (plugging/reversing, high inrush) the contactor is rated 15.5 A at 400 V, so it handles the severe switching of motor reversing or jogging applications. For resistive loads (AC-12) it carries 10 A maximum. DC switching is also covered: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — useful for DC brake coils or small DC motor circuits. The contactor is rated for a mechanical life of 10,000,000 operations. The front is IP20 (finger-safe), the terminals are IP00 (touch-hazard if live).
Width is 45 mm, height 85 mm, depth 140 mm. Side clearance of 6 mm is needed only if not mounted side-by-side. Main terminals accept screw-type connections: 2x (1 to 2.5 mm²) or 2x (2.5 to 6 mm²) solid/stranded, max 2x 10 mm². Auxiliary terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²), max 2x 4 mm². AWG equivalents for main: 2x (16 to 12), 2x (14 to 10), 1x 8.
Protection and coordination
This lets the panel builder size the branch protection correctly.