Skip to main content
Siemens 3RT1026-1AG60 — Contactors

Siemens 3RT1026-1AG60 SIRIUS Power Contactor, S0, 11 kW at 4

MPN3RT1026-1AG60

Siemens SIRIUS S0 power contactor, 3RT1026-1AG60, screw-type terminals, 11 kW rated at 400 V AC-2, 15.5 A AC-4, 45 mm width, for 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1026-1AG60 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-1AG60 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-1AG60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz100 V
3RT1026-1AG60 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-1AG60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-1AG60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1026-1AG60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1026-1AG60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1026-1AG60 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth91 mm

Product details

The Siemens 3RT1026-1AG60 is a SIRIUS S0-frame power contactor with screw-type terminals on the main circuit, rated for motor switching at 11 kW in AC-2 duty at 400 V and 15.5 A in AC-4 duty at 400 V. It also handles 11 kW at 690 V, so it covers 400 V and 690 V motor loads without a frame size bump. It mounts on a 35 mm DIN rail per EN 50022, with a 45 mm width and 85 mm height — a standard S0 footprint that fits alongside other SIRIUS components in a control panel. Side-by-side mounting is allowed, with a 6 mm clearance required at the side.

Motor ratings and coordination

The AC-2 rating (11 kW at 400 V) covers slip-ring motor starting and reversing; the AC-4 rating (15.5 A at 400 V) covers plugging and inching duty where the contactor makes and breaks stalled-rotor current. For general squirrel-cage motor starting (AC-3), the 690 V rating at 11 kW gives a sense of the thermal capacity — the contactor is sized for motors up to that power class. Short-circuit coordination: with type 2 coordination (limited damage), use a gL/gG fuse rated 35 A. With type 1 coordination (replace contactor after fault), a 100 A gL/gG fuse is allowed. These figures govern the upstream protection selection for the motor branch circuit. Auxiliary contacts are rated for switching at various control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. The DC switching capacity drops sharply with voltage — the 220 V DC rating at 0.3 A is typical for a contactor of this size.

Main circuit screw terminals accept solid/stranded conductors: 2x (1... 2.5 mm²), 2x (2.5... 6 mm²), or a single 10 mm². Auxiliary terminals take 2x (0.5... 1.5 mm²) or 2x (0.75... 2.5 mm²), max 2x 4 mm². AWG equivalents are 2x (16... 12) and 2x (14... 10) for main, with a single 8 AWG maximum. Coil operating range: 0.8... 1.1 × rated voltage at 50 Hz, 0.85... 1.1 at 60 Hz. The coil is rated for both 50 Hz and 60 Hz supply, with a nominal voltage of 100 V at 50 Hz and 100... 110 V at 60 Hz.

For a BOM freeze or critical spare, this part is a fast mover — the S0 frame is one of the most common contactor sizes in European panel builds. Keep one on the shelf if your line runs 11 kW motors at 400 V.

Frequently asked questions

What are the motor power ratings for 3RT1026-1AG60 at 400 V and 690 V?

At 400 V AC-2 duty it is rated 11 kW; at 690 V AC-2 it is also rated 11 kW. The AC-4 current rating at 400 V is 15.5 A.

What fuse is required for type 2 coordination with 3RT1026-1AG60?

For type 2 coordination (limited damage after a short circuit), use a gL/gG fuse rated 35 A. For type 1 coordination, a 100 A gL/gG fuse is permitted.

Where can I buy 3RT1026-1AG60 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

Will 3RT1026-1AG60 drop into a panel specified around 3RT1023-1AL20?

Both are SIRIUS S0-frame contactors with the same 45 mm width and DIN-rail mounting, so the mechanical footprint is identical. The difference is in the coil voltage and power ratings — the 3RT1026-1AG60 has a 100 V AC coil, while the 3RT1023-1AL20 has a different coil. Verify coil voltage compatibility before swapping.

MPN
3RT1026-1AG60