The same 11 kW rating at 690 V means it can serve higher-voltage motor circuits without derating the power throughput. The contactor carries a mechanical service life of 10 million operations, which suits applications with frequent switching cycles like conveyor systems or pump controls.
For type 2 coordination (no weld after a short circuit), the upstream fuse must be gL/gG rated at 35 A. For type 1 coordination (device may be damaged but no fire risk), a 100 A gL/gG fuse is the limit. This matters when the contactor sits in a panel with a high-fault-capacity bus. The auxiliary contact block provides 2 instantaneous contacts, which is enough for a basic feedback circuit to a PLC or a holding contact for the coil.
Width is 45 mm, height 85 mm, depth 140 mm. Side-by-side mounting is permitted with zero spacing — the 6 mm side clearance listed is for heat dissipation when mounted individually, but the contactor is designed for zero-gap grouping on the rail. Main circuit terminals accept 2x (1 to 2.5 mm²) or 2x (2.5 to 6 mm²) stranded, or up to 2x 10 mm² solid. The auxiliary circuit terminals take 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid, with a maximum of 2x (0.75 to 4 mm²). AWG equivalents are 2x (16 to 12) or 2x (14 to 10) for main, and 1x 8 for a single larger conductor.