It delivers 11 kW at 400 V in AC-2 use (slip-ring motors, moderate overloads) and carries a 15.5 A continuous rating in AC-4 (plugging, inching, reversing). At 45 mm wide and 85 mm tall, it fits a standard S0 footprint — same slot as other SIRIUS S0 contactors, so swapping one in doesn't force a panel layout change.
The AC-2 motor rating of 11 kW at 400 V covers most medium-duty pump and fan loads. For type 2 coordination (fault withstand without welding), the spec calls for a 35 A gL/gG fuse upstream. If you're running type 1 coordination (replace contactor after fault), a 100 A fuse is allowed — that's a wide window for selectivity with upstream breakers. The auxiliary circuit (if fitted) uses the smaller 0.5–4 mm² range. That's enough for a 35 A feeder on the mains and standard 1.5 mm² control wiring.