Skip to main content
Siemens 3RT1026-1AN24-ZX95 — Contactors

Siemens 3RT1026-1AN24-ZX95 SIRIUS Power Contactor, S0, 11 kW

MPN3RT1026-1AN24-ZX95

Siemens SIRIUS power contactor, size S0, 3RT1026-1AN24-ZX95, 11 kW at 400 V AC-2, screw-type terminals, 45 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1026-1AN24-ZX95 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-1AN24-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-1AN24-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz220 V
3RT1026-1AN24-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-1AN24-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-1AN24-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1026-1AN24-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1026-1AN24-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1026-1AN24-ZX95 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth140 mm

Product details

It's rated for 11 kW at 400 V in AC-2 duty, which covers slip-ring motor starting and reversing applications. The 45 mm width and screw-and-snap-on mounting to 35 mm DIN rail (DIN EN 50022) mean it fits standard panel layouts without special adapters.

The AC-4 rating of 15.5 A at 400 V is the one to watch for plugging or inching duty — that's the higher-stress switching cycle where the contactor makes and breaks full motor current. For AC-2 (slip-ring motors), the 11 kW rating at 400 V governs. The operating current at AC-12 (resistive load) maxes out at 10 A. If you're coordinating with upstream protection, Type 1 coordination calls for a 100 A gL/gG fuse; Type 2 requires 35 A. The operating temperature range of -25 to +60 °C covers most indoor panel environments, and the degree of pollution 3 rating means it's suited for industrial atmospheres with conductive dust or moisture.

Main current circuit connections are screw-type terminals accepting 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, up to max 2x 4 mm². For AWG, that's 2x (16 to 12) solid, 2x (14 to 10) stranded, or 1x 8.

Frequently asked questions

What are the key dimensions for panel layout?

Width is 45 mm, height 85 mm, depth 140 mm. Side clearance of 6 mm is specified for side-by-side mounting.

What fuse coordination is required?

Type 1 coordination requires a 100 A gL/gG fuse. Type 2 coordination requires a 35 A gL/gG fuse.

MPN