Siemens 3RT1026-1AP60 — Contactors

Siemens 3RT1026-1AP60 SIRIUS Power Contactor, 11 kW at 400 V

MPN3RT1026-1AP60

Siemens SIRIUS, power contactor, size S0, 3RT1026-1AP60, 11 kW at 400 V AC-3, 24 VDC coil, screw terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1026-1AP60 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-1AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V11 kW
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-1AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz220 V
3RT1026-1AP60 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-1AP60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-1AP60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1026-1AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1026-1AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Installation altitude, max.2 000 m
3RT1026-1AP60 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth91 mm

Product details

What the 3RT1026-1AP60 is and what it does

The Siemens 3RT1026-1AP60 is a SIRIUS power contactor in the S0 frame size, designed for switching three-phase motor loads in industrial control panels. Its headline rating is 11 kW at 400 V in AC-3 duty, which means it handles the high inrush of induction motors up to that power level without welding contacts. The 24 VDC coil draws 10 A at its rated voltage, so confirm your control transformer can support that inrush if multiple contactors pull in simultaneously.

Mounting and panel integration

Mounts via screw or snap-on onto 35 mm DIN rail per EN 50022. The S0 footprint is 45 mm wide, 85 mm tall, and 91 mm deep — that 91 mm depth is the dimension to watch when sizing the enclosure depth or gland plate clearance. Side-by-side mounting is permitted with 6 mm spacing at the side, so you can pack multiple contactors on a rail without derating for heat buildup.

Wiring and terminal specs

Main current circuit uses screw-type terminals. Solid wire capacity is 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). For stranded wire, it accepts 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), or max 2x 10 mm². AWG equivalents are 2x (16 to 12), 2x (14 to 10), or 1x 8. The front face carries an IP20 touch-safe rating; the terminal area itself is IP00, so maintain safe clearance in the enclosure.

Coordination and protection

For Type 2 coordination (no damage to the contactor under short circuit), the required upstream fuse is gL/gG 35 A. For Type 1 coordination (contactor may need replacement after a fault), the fuse can be gL/gG 100 A. The pollution degree is 3, meaning it's rated for industrial environments with conductive pollution — no conformal coating required for normal panel conditions.

Frequently asked questions

What are the key ratings for the 3RT1026-1AP60?

The headline motor rating is 11 kW at 400 V AC-3. The coil is 24 VDC, drawing 10 A at rated voltage. It also carries 11 kW at 690 V AC-3, and the AC-4 (reversing/plugging) current is 15.5 A at 400 V.

What is the depth of the 3RT1026-1AP60?

The depth is 91 mm. This is the dimension from the DIN rail mounting surface to the furthest point of the contactor body, critical for enclosure depth planning.

What wire sizes does the 3RT1026-1AP60 accept?

Solid wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). Stranded: 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), or max 2x 10 mm². AWG: 2x (16 to 12), 2x (14 to 10), or 1x 8.

Will the 3RT1026-1AP60 drop into a panel designed for the 3RT1023-1AL20?

Both are S0 frame contactors with the same 45 mm width and DIN rail mounting, so the mechanical footprint is identical. The difference is in the coil voltage and power rating — verify the 3RT1026-1AP60's 24 VDC coil and 11 kW rating match your circuit requirements before substituting.

MPN