SIRIUS S0 Power Contactor — 3 NO, 11 kW AC-2 at 400 V
It is rated for 11 kW at 400 V under AC-2 duty (slip-ring motor switching) and delivers 15.5 A at 400 V under AC-4 duty (plugging/reversing/inching).
Coordination & Protection
Type 1 coordination (contactor may need replacement after fault) allows a 100 A gL/gG fuse. This gives the panel designer flexibility: use the 35 A fuse where uptime matters, or the 100 A where fault-clearing capacity is the priority.
Termination & Wiring
Main circuit terminals are screw-type, accepting 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or max 2x (0.75...4 mm²) solid/stranded, with AWG equivalents 2x (16...12), 2x (14...10), or 1x 8. Auxiliary/control circuit terminals accept 2x (1...2.5 mm²) or 2x (2.5...6 mm²) solid/stranded, max 2x 10 mm², AWG 2x (20...16), 2x (18...14), or 1x 12.
