For AC-3 duty (normal motor start/stop), it's rated for 11 kW at 500 V and 11 kW at 690 V, covering common three-phase motor sizes across 400-690 V line supplies. The coil draws 5.4 W on DC hold — a continuous-duty coil that stays cool in a sealed enclosure, so no derating needed for the holding power.
Main circuit terminals accept screw-type connections: 2x (0.5...1.5 mm²) solid, 2x (0.75...2.5 mm²) stranded, up to 2x 4 mm² max. For AWG, that's 2x (16...12) solid, 2x (14...10) stranded, or 1x 8. At altitudes above 2,000 m, derate the thermal current.
Sizing and coordination
For Type 1 coordination (replace the contactor after a fault), use a 100 A gL/gG fuse. These values govern your branch circuit protection design. The auxiliary contact block has 2 instantaneous contacts (NO/NC configurable).