Rated 11 kW at 400 V in AC-2 duty (slip-ring motors, soft-start applications) and 11 kW at both 500 V and 690 V, this contactor handles the common European motor voltages. For resistive loads (AC-12), it carries 10 A continuously. The screw-type main terminals accept up to 10 mm² stranded or 4 mm² solid conductors, with dual-wire capability for daisy-chaining.
Type 1 coordination (contactor may need replacement but the circuit is cleared) allows up to 100 A gL/gG. This matters when you're specifying upstream protection for a motor branch circuit.
Dimensions and Environment
Side-by-side mounting is allowed with a 6 mm gap to adjacent devices for heat dissipation. The terminal area is IP00 — safe inside an enclosure but not touch-safe open. Maximum operating altitude is 2000 m without derating, covering most installations.