Skip to main content
Siemens 3RT1026-1HB40 — Contactors

Siemens SIRIUS 3RT1026-1HB40 Power Contactor, 24 V DC Coil,

MPN3RT1026-1HB40

Siemens SIRIUS power contactor, 3RT1026-1HB40, S0 frame, 24 V DC coil, 11 kW at 400 V AC-2, 45 mm width, screw terminals, IP20 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1026-1HB40 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-1HB40 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-1HB40 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT1026-1HB40 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-1HB40 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-1HB40 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Side-by-side mountingYes
3RT1026-1HB40 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
3RT1026-1HB40 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1026-1HB40 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth101 mm

Product details

The Siemens SIRIUS 3RT1026-1HB40 is a S0-frame power contactor rated for motor switching in industrial control panels. Its 24 V DC coil draws 4.2 W during both closing and holding, so the coil supply can be a standard 24 V DC power supply without oversizing for inrush. The main contacts are screw-type terminals sized for 2x (0.75... 4 mm²) solid or 2x 10 mm² stranded, which covers most motor leads up to 11 kW. At 400 V, the AC-2 rating is 11 kW — that is the duty for slip-ring motors or moderate starting. For reversing or plugging duty (AC-4), the same contactor handles 15.5 A at 400 V. The AC-12 maximum operating current is 10 A, which covers resistive loads like heater banks. Type 2 coordination requires a 35 A gL/gG fuse upstream; Type 1 allows a 100 A fuse, giving flexibility in panel design.

Front protection is IP20; the terminals themselves are IP00, meaning the panel enclosure provides the environmental seal. Maximum operating altitude is 2000 m, so it is fine for most plant-floor installations without derating. Mechanical endurance is 10 million operations — a fast mover for high-cycle applications like conveyor lines.

Auxiliary contacts and wiring

The contactor carries no instantaneous auxiliary contact as standard (0 auxiliary contacts), so if you need feedback or interlocking, order a separate auxiliary contact block. The auxiliary contact ratings are: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V — all at the rated value. Wire sizes for the main circuit accept 2x (16... 12) AWG solid or 1x 8 AWG stranded.

Frequently asked questions

What are the key ratings for motor switching?

At 400 V AC-2 duty, it is rated 11 kW. For AC-4 reversing duty at 400 V, the current rating is 15.5 A. The AC-12 resistive load maximum is 10 A.

What is the physical size and how does it mount?

The S0 frame is 45 mm wide, 85 mm tall, and 101 mm deep. It snaps onto 35 mm DIN rail per EN 50022, and side-by-side mounting is allowed with 6 mm side clearance.

What wire sizes does the main circuit accept?

Solid conductors: 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), max 2x (0.75... 4 mm²). Stranded: 2x (1... 2.5 mm²), 2x (2.5... 6 mm²), max 2x 10 mm². AWG equivalents: 2x (16... 12) solid, 1x 8 stranded.

Does the 3RT1026-1HB40 include auxiliary contacts?

No. It has zero instantaneous auxiliary contacts as standard. An auxiliary contact block must be ordered separately if needed for status feedback or interlocking.

MPN
3RT1026-1HB40