Rated for 11 kW at 400 V in AC-2 duty (slip-ring motor starting) and 15.5 A at 400 V in AC-4 duty (plugging/inching), this contactor handles the high inrush and frequent switching cycles of demanding motor applications. The main circuit connects via screw-type terminals accepting 2x (0.25...2.5 mm²) solid or 2x (1...2.5 mm²) stranded, up to 2x 10 mm² maximum — sized for the S0 frame's current range.
Key ratings in context
At 500 V and 690 V, the contactor is rated for 11 kW in AC-3 duty (squirrel-cage motor starting), which covers the bulk of standard induction motor switching on 400/480 V and 690 V networks. Type 1 coordination allows a 100 A fuse. This tells the panel builder what upstream protection keeps the contactor repairable after a fault.
Side-by-side mounting is permitted with zero clearance, so multiple contactors can pack tightly on the rail.