The contactor carries 3 NO main contacts and no NC main contacts, with two instantaneous auxiliary contacts available for feedback or interlock wiring.
Rated at 11 kW at 400 V AC-3 and also 11 kW at 690 V AC-3, this contactor handles standard three-phase induction motors up to that power. The AC-4 rating of 15.5 A at 400 V covers reversing or inching duty where the contactor makes and breaks stalled rotor current — a tougher thermal cycle than AC-3. For type 2 coordination (no weld risk on fault), use a 35 A gL/gG fuse upstream. The contactor's mechanical life is rated at 10,000,000 operations typical, and the operating temperature range is -25 to +60 °C. The front face carries IP20 finger protection; the terminals themselves are IP00, so the panel enclosure must provide the environmental seal.
Mounting and integration into your panel
The auxiliary contact block (2 instantaneous contacts) shares the same coil suppression as the main contactor — verify free-wheel diode polarity if you're adding a DC suppressor across the coil terminals.
No substitute or second-source cross-reference is required at this time.