It's rated 11 kW at 400 V for AC-2 duty (slip-ring motor starting) and 15.5 A at 400 V for AC-4 duty (plugging/reversing/inching).
Terminal & wiring
Main circuit terminals accept 2x (1 to 2.5 mm²) solid or stranded, 2x (2.5 to 6 mm²), or a single 10 mm² conductor. AWG equivalents: 2x (16 to 12), 2x (14 to 10), or 1x 8. The coil terminals accept 2x (0.25 to 2.5 mm²) solid. Strip and torque per the nameplate — the screw terminals are standard for panel builds.
Coordination & protection
For type 1 coordination (device may be damaged but no fire risk), a 100 A gL/gG fuse is permitted.