Skip to main content
Siemens 3RT1026-3AL28-1MA2 — Contactors

Siemens 3RT1026-3AL28-1MA2 SIRIUS Power Contactor, S0, 11 kW

MPN3RT1026-3AL28-1MA2

Siemens SIRIUS 3RT1026-3AL28-1MA2 power contactor, size S0, screw-type terminals, 230 V 50/60 Hz coil, 11 kW at 400 V AC-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT1026-3AL28-1MA2 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-3AL28-1MA2 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-3AL28-1MA2 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz230 V
3RT1026-3AL28-1MA2 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-3AL28-1MA2 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-3AL28-1MA2 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Side-by-side mountingYes
3RT1026-3AL28-1MA2 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1026-3AL28-1MA2 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
3RT1026-3AL28-1MA2 — Mechanical
ParameterValue
Width45 mm
Height85 mm
Depth140 mm

Product details

The Siemens SIRIUS 3RT1026-3AL28-1MA2 is a size S0 power contactor with a 230 V 50/60 Hz coil, designed for switching motor loads in control panels. Rated for 11 kW at 400 V in AC-2 duty (slip-ring motors) and 15.5 A in AC-4 duty (reversing/inching), this contactor handles the demanding switching cycles of conveyor drives, pumps, and compressors. The three main poles use screw-type terminals accepting up to 2x 10 mm² or 1x 8 AWG, with a solid wire range of 0.25 to 2.5 mm² on the auxiliary contacts. A built-in 3-pole auxiliary contact block provides instantaneous signalling for feedback or interlocking.

Coil and auxiliary contact ratings

The 230 V coil operates at 50 Hz and 60 Hz with an operating factor range of 0.8 to 1.1 at 50 Hz and 0.85 to 1.1 at 60 Hz, meaning it picks up reliably even with a sagging line. The auxiliary contacts are rated for 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — sufficient for PLC input cards or small relay loads.

Environmental and coordination specs

The front face carries IP20 finger protection; the terminals are IP00 — panel builders must ensure terminal shrouding or enclosure clearance.

Compliance documentation typically includes CE, UL, CSA, and IEC 60947-4-1 certification for the SIRIUS series. RoHS and REACH declarations are standard from Siemens for this product family.

Frequently asked questions

What are the key ratings for this contactor?

It is rated for 11 kW at 400 V AC-2 and 15.5 A at 400 V AC-4. The coil is 230 V 50/60 Hz. Main terminals accept up to 2x 10 mm² or 1x 8 AWG. It has 3 auxiliary contacts rated at 10 A at 24 V.

What is the physical size and mounting?

Width is 45 mm, height 85 mm, depth 140 mm. It snaps onto 35 mm DIN rail per EN 50022, and side-by-side mounting is permitted without derating.

What short-circuit protection is required?

For Type 2 coordination (no damage to the contactor after a fault), use a gL/gG fuse rated at 35 A. For Type 1 coordination (contactor may need replacement), a 100 A fuse is allowed.

How does this compare to the 3RT1034-1AN60-1AA0?

The 3RT1034-1AN60-1AA0 is a larger frame size (S2 vs S0) with higher current ratings and a different coil voltage. It will not drop into a panel designed for the S0 3RT1026 without rewiring and a larger DIN footprint. The 3RT1026-3AL28-1MA2 is the correct fit for S0-based designs.

MPN
3RT1026-3AL28-1MA2