In AC-4 duty (inching, reversing under load), it switches 15.5 A at 400 V. The AC-12 rating of 10 A covers resistive loads.
Main circuit terminals are screw-type, accepting 2x (1 to 2.5 mm²) solid/stranded, 2x (2.5 to 6 mm²), or up to 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), or 1x 8. The auxiliary contact terminals accept 2x (0.25 to 2.5 mm²). For Type 1 coordination (no damage under short circuit), use a gL/gG fuse rated 100 A. For Type 2 coordination (limited damage, device remains usable), the fuse drops to 35 A.