Specifications

3RT1026-3XB44-0LA2 — Identification
ParameterValue
Contactor frame sizeS0
3RT1026-3XB44-0LA2 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V15.5 A
Rated value @ 400 V3 A
Rated value @ 500 V11 kW
Rated value @ 690 V11 kW
Rated value @ 230 V3 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT1026-3XB44-0LA2 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT1026-3XB44-0LA2 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT1026-3XB44-0LA2 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 100 A
Short-circuit coordination type 2, fusefuse gL/gG: 35 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT1026-3XB44-0LA2 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.25 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.25 ... 1.5 mm²)
Side-by-side mountingYes
3RT1026-3XB44-0LA2 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT1026-3XB44-0LA2 — Mechanical
ParameterValue
Width45 mm
Height119 mm
Depth150 mm

Product details

The 24 VDC coil draws 10 A at 24 V rated value, dropping to 2 A at 60 V and 1 A at 110 V — that tells you the control-circuit power supply needs to handle the inrush. For motor loads, the contactor is rated 3 hp at 230 V, 7.5 hp at 200/208 V, 7.5 hp at 220/230 V, 15 hp at 460/480 V, and 20 hp at 575/600 V. At 400 V it switches 3 A in AC-4 duty (15.5 A), meaning it handles the high-stress reversing or inching cycles where the contacts break full motor current.

The contactor measures 45 mm wide, 119 mm tall, and 150 mm deep. The front face carries an IP20 rating (finger-safe), while the terminals themselves are IP00 — meaning the wiring compartment is open and needs enclosure protection in dusty or wet environments.

Frequently asked questions

Where can I buy 3RT1026-3XB44-0LA2 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here.

What is the closest functional second-source to 3RT1026-3XB44-0LA2?

The closest peer in the same S0 frame is 3RT1026-1AB00, which shares the same S0 size and screw-terminal format but differs in coil voltage and auxiliary contact configuration. The 3RT1026-3XB44-0LA2 carries a 24 VDC coil and two instantaneous auxiliary contacts; the 3RT1026-1AB00 uses a different coil voltage. Verify coil compatibility before swapping.

What is the depth of 3RT1026-3XB44-0LA2?

The depth is 150 mm, which is standard for the S0 frame size and fits most DIN-rail enclosures with that clearance.

What wire sizes does the 3RT1026-3XB44-0LA2 accept?

The solid/stranded terminals accept 2x (0.25... 2.5 mm²) for auxiliary wiring, and the main circuit terminals accept 2x (1... 2.5 mm²), 2x (2.5... 6 mm²), or max. 2x 10 mm².

Will 3RT1026-3XB44-0LA2 drop into a panel specified around 3RT1026-1AB00 without rewiring?

Mechanically yes — both are S0 frame, same DIN-rail footprint and screw-terminal layout. Electrically no: the coil voltage differs (24 VDC vs the 1AB00's coil), so the control circuit must match. Check the coil rating before swapping.