AC-4 at 400 V is 15.5 A, covering plugging and inching duty where the contactor opens under full motor current. That's fast enough for most sequencing applications but worth noting if you're coordinating with PLC scan cycles or safety relay timing. The enclosure is IP20 on the front, IP00 at the terminals — meaning the wiring zone needs to be inside a cabinet or protected from accidental contact.
RoHS compliance date is May 1, 2012, so it meets the EU directive. No UL or CSA marks are listed in the spec sheet, but the SIRIUS line typically carries IEC ratings for global panels. If your project requires a specific agency approval, confirm at quote time.
Dimensions are 55 mm wide, 112 mm high, 130 mm deep. That's a standard S2 footprint — it shares the same mounting hole pattern and terminal layout as other SIRIUS S2 contactors, so swapping in a different coil voltage or auxiliary block doesn't require re-drilling the subpanel. That gives flexibility for both control wiring (smaller gauges) and power wiring (larger gauges) without needing adapter lugs.