Rated motor power: 18.5 kW at 500 V (60 Hz) and 10 kW at 690 V (60 Hz), and 15 kW at 400 V under AC-2 duty. That covers standard three-phase induction motors on 400 V, 480 V, and 690 V grids. Auxiliary contacts handle 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for control-circuit interlocking or status feedback. The coil hold-in range is 0.8 to 1.1 times rated voltage at 60 Hz, with an arcing time of 10 to 15 ms.
The contactor is 55 mm wide and 115 mm deep, with a height of 112 mm. It mounts side-by-side without derating (side-by-side mounting is permitted). For a panel builder, that means you can land a 16 mm² stranded cable on the main circuit and still have room for auxiliary wiring.