It carries a 110 V coil and is rated for AC-4 duty at 29 A at 400 V, meaning it can handle severe inrush and plugging duty for motors up to that current. At 500 V it is rated for 18.5 kW motor output, and at 690 V for 10 kW. The main circuit uses screw-type terminals, accepting solid wires from 0.25 to 2.5 mm² and stranded wires from 0.75 to 25 mm².
The AC-2 rating at 15 kW at 400 V covers slip-ring motor starting. For resistive loads (AC-1), the maximum switching frequency is 1200 operations per hour; for AC-3 (standard squirrel-cage motor start/run) it is 1000 ops/h, and for AC-4 it drops to 250 ops/h due to the heavier electrical wear. The auxiliary contact ratings at 24 V (10 A), 110 V (1 A), and 230 V (6 A) cover typical PLC or relay interface levels.
Dimensions: width 55 mm, height 112 mm, depth 130 mm. The contactor is rated for use in enclosures with pollution degree 3.