It is rated for 18.5 kW at 500 V and 10 kW at 690 V, with a 24 VDC coil.
Side-by-side mounting is permitted, which simplifies multi-contactor panel layouts. Dimensions are 55 mm wide, 129 mm high, and 164 mm deep.
Terminal and Wiring Capacity
The main circuit terminals accept solid conductors 2x (0.25 to 2.5 mm²) and stranded conductors 2x (0.75 to 25 mm²) or 2x (0.75 to 16 mm²). This range covers common motor and control wiring sizes used in panel building.
Shock resistance is 15g at 5 ms and 8g at 10 ms under AC conditions.
Maximum switching frequency varies by duty: 1,200 operations/hour at AC-1 (resistive), 750 at AC-2 (slip-ring motor), 1,000 at AC-3 (squirrel-cage motor), and 250 at AC-4 (plugging/inching). DC dropout delay is 20 to 30 ms. Operating range factor is 0.8 to 1.1 at 50 Hz and 0.85 to 1.1 at 60 Hz.
Auxiliary contacts are rated: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V. These are the continuous current ratings for the auxiliary circuit.